Research Info

Home \ارایه الگوریتم مکان یابی خطای ...
Title ارايه الگوريتم مكان يابي خطاي دقيق در شبكه هاي توزيع هوشمند مجهز شده به ميكرو PMUها
Type Presentation
Keywords fault location, load estimation, equivalent impedance, observability, impedance-based method
Abstract Faults in electrical distribution systems are among the main causes for power disruption and outage. Therefore, it is necessary to locate faults accurately and quickly. This paper proposes an accurate impedance-based algorithm to locate faults in smart distribution network. The network has become fully observable with the minimum number of micro phasor measurement units (?PMUs). Distributed line parameters model is used to improve fault location algorithm in terms of accuracy. Since the impedance-based algorithms are sensitive to the load impedance of each node, the current and voltage of all nodes are calculated using pre-fault recorded current and voltage by each ?PMU. The load impedance of each node and subsequently, the equivalent impedance at the end of every section is calculated. The performance of the proposed algorithm is investigated on an observable IEEE 34 Node Test Feeder under various fault conditions such as: different types of fault, distances, resistances and fault inception angles. In addition, to for further demonstration, practical tests are performed.
Researchers hamid mirshekali (First researcher) , Rahman Dashti (Second researcher) , hamidreza shaaker (Third researcher)